Product model: HYVA-405    
Product introduction:       
1 Tests for Current Transformer:            
1 Excitation curve and parameters test             
2 Turns ratio test             
3 Ratio and phase error test             
4 Polarity mark check             
5 Winding resistance measurement             
6 Secondary loop burden measurement             
7 Error line curve test for protection CT             
8 Transient CT parameters test             
9 CT nameplate guess             
10 Saturation hysteresis loop curve measurement            
1 Tests for Voltage Transformer:            
1 Turns ratio test             
2 Ratio error and phase angle error test             
3 Polarity test             
4 Secondary burden test             
5 Winding resistance test            
Product technical index:  
1 Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13             
2 Power supply: AC220V±10%, 50/60Hz±10%             
3 Voltage output: 0.1~180V (AC)             
4 Current output: 0.001~5A(RMS)             
5 Power output: 500VA             
6 Maximum knee voltage measurement: 45KV             
7 Current measurement:             
  Range: 0~10A (automatically change range in 0.1/0.4/2/10A)              
  Error: <±0.1%+0.01%FS             
8 Voltage measurement:             
  Range: 0~200V (automatically change range in 1V/10V/70V/200V)             
  Error: < ±0.1%+0.01%FS             
9 Turns ratio measurement:             
  Range:1~35000             
  1~2000          error<0.05%             
  2000~5000    error<0.1%             
  5000~35000  error<0.2%             
10 Phase measurement: error: ±2min; resolution: 0.01min             
11 Winding resistance measurement:              
  Range: 0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)             
  Error: < 0.2%RDG+0.02%FS             
  Maximum resolution: 0.1mΩ             
12 Temperature measurement:-50~100 Celsius degree; error<3 Celsius degree             
13 CT Secondary burden:             
  Range: 0160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)             
  Error: <0.2%RDG+0.02%FS              
  Maximum resolution: 0.001ohm             
14 PT Secondary burden:             
  Range: 080kohm (automatically change range in 800ohm/8kohm/80kohm)             
  Error :<0.2%RDG+0.02%FS              
  Maximum resolution: 0.1ohm             
15 PT ratio measurement:             
  Range: 1~35000             
  1~10000 error<0.1%             
  10000~35000 error<0.2%             
16 PT ratio error measurement: Typical error <0.05%, Maximum Error<0.1%             
17 PT phase angle measurement: maximum error < 3min             
18 Make evaluation for test results according to selected standards             
19 Make word report for test result             
20 Make word reports one time for multi-group test records on the PC             
21 Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test             
22 Compare excitation curves with saved excitation curves in the same window             
23 Memory capacity: >1000 groups test results              
24 Working condition: temperature: -10℃~50; moist: ≤90%             
25 Size: 485mm×356mm×183mm             
26 Weight: <15kg            
Product tags:

ct pt analyzer, current transformer analyzer, ct analyzer, pt analyzer, ct tester, pt tester, 

current transformer testing equipment, current transformer manufacturer, current transformer maker,

hyva-405 series maker, electrical test equipment, hv test equipment.

 