1. General specification for EKQ2
EKQ2 series electromagnetic starter ( "starter" for short hereinafter) applies mainly to circuit with AC current of 50Hz (or 60Hz), rated operational voltage of 660V and rated controlled power up to 45kW (current up to 95A) for using to control the direct start and halt of the electromotor to protect the motor from overload and phase failure.
2. Features of starter
1. 3-phase bimetal
2. Temperature compensation
3. Test button
4. Stop button
5. Manual and automatic reset button
6. Electrically separated 1N/O plus 1N/C contact
3. Wiring Diagram
4. Overall and Mounting Dimensions (mm)
EKQ2-09~32(Plastic base + Plastic cover) EKQ2-40~95(Steel base + Plastic cover)
Model | Range of setting current A | Current(A) | Maximum rated Power(KW) | Model of equipped AC Contactor | TOR Matched | ||
AC-3 | |||||||
660V | 380V | 220V | |||||
EKQ2-09/1301 | 0.1~0.16 | 9 | 5.5 | 4 | 2.2 | EKC1-09 | EKR2-13 |
EKQ2-09/1302 | 0.16~0.25 | ||||||
EKQ2-09/1303 | 0.25~0.4 | ||||||
EKQ2-09/1304 | 0.4~0.63 | ||||||
EKQ2-09/1305 | 0.63~1 | ||||||
EKQ2-09/1306 | 1~1.6 | ||||||
EKQ2-09/1307 | 1.6~2.5 | ||||||
EKQ2-09/1308 | 2.5~4 | ||||||
EKQ2-09/1310 | 4~6 | ||||||
EKQ2-09/1312 | 5.5~8 | ||||||
EKQ2-09/1314 | 7~10 | ||||||
EKQ2-18/1314 | 7~10 | 18 | 10 | 7.5 | 4 | EKC1-18 | EKR2-13 |
EKQ2-18/1316 | 9~13 | ||||||
EKQ2-18/1321 | 12~18 | ||||||
EKQ2-25/1321 | 12~18 | 25 | 15 | 11 | 5.5 | EKC1-25 | EKR2-13 |
EKQ2-25/1322 | 17~25 | ||||||
EKQ2-32/2353 | 23~32 | 32 | 18.5 | 15 | 7.5 | EKC1-32 | EKR2-23 |
EKQ2-40/3353 | 30~40 | 40 | 30 | 18.5 | 11 | EKC1-40 | EKR2-33 |
EKQ2-50/3357 | 37~50 | 50 | 33 | 22 | 15 | EKC1-50 | EKR2-33 |
EKQ2-65/3359 | 48~65 | 65 | 37 | 30 | 18.5 | EKC1-65 | ELR2-33 |
EKQ2-80/3361 | 55~70 | 80 | 45 | 37 | 22 | EKC1-680 | EKR2-33 |
EKQ2-80/3353 | 63~80 | ||||||
EKQ2-95/3365 | 80~93 | 95 | 45 | 45 | 25 | EKC1-95 | EKR2-33 |